① before the safety gas aluminum valves factory,
should one by one to adjust the opening pressure setting value of user
requirements. If the user make spring working pressure level, the
general should be adjusted lower limit of the pressure level of the
factory.
② user before the safety valve is installed on the
protected equipment or before installation, you must re-adjusted at the
installation site, in order to ensure that the setting pressure relief
valve to meet the requirements.
③ spring working pressure level
within the range of nameplate by the rotation adjustment screw to change
the amount of compression spring can be adjusted to opening pressure.
④ Before the rotation adjustment screw, the Water Heater Gas Valves inlet
pressure should be reduced to 90% of the opening pressure of the
following, in order to prevent the valve is rotated when the rotation
adjustment screw, which damage the sealing surface.
⑤ To ensure
accurate opening pressure value, should make adjustments in the medium
conditions, such as media type, temperature as close to the actual
operating conditions. Media types to change, especially when the media
is not the same accumulation of state (for example, from liquid into
vapor), the opening pressure changes often. When the temperature
increases, the opening pressure is generally decreased. It is adjusted
at room temperature and used at high temperatures, the set pressure
value at room temperature should be slightly higher than the required
opening pressure. To what extent the valve structure and material
selection have a relationship should be based according to the
manufacturer's instructions.